2601.10976

Total: 1

#1 Determining optimal thermal energy storage charging temperature for cooling using integrated building and coil modeling [PDF] [Copy] [Kimi] [REL]

Authors: Ju-Hong Oh, Seon-In Kim, Eui-Jong Kim

Thermal energy storage (TES) systems coupled with heat pumps offer significant potential for improving building energy efficiency by shifting electricity demand to off-peak hours. However, conventional operating strategies maintain conservatively low chilled water temperatures throughout the cooling season, a practice that results in suboptimal heat pump performance. This study proposes a physics-based integrated simulation framework to determine the maximum feasible chilled water supply temperature while ensuring cooling stability. The framework integrates four submodels: relative humidity prediction, dynamic cooling load estimation, cooling coil performance prediction, and TES discharge temperature prediction. Validation against measured data from an office building demonstrates reliable accuracy across all sub-models (e.g., CVRMSE of 9.3% for cooling load and R2 of 0.91 for peak-time discharge temperature). The integrated simulation reveals that the proposed framework can increase the daily initial TES charging temperature by an average of 2.55 °C compared to conventional fixed-temperature operation, enabling the heat pump to operate at a higher coefficient of performance. This study contributes a practical methodology for optimizing TES charging temperatures in building heating, ventilation, and air conditioning (HVAC) systems while maintaining indoor setpoint temperatures.

Subject: Systems and Control

Publish: 2026-01-16 03:39:41 UTC