Total: 1
Controller synthesis in power electronics-based systems depends predominantly on the mathematical model of the system, which is a limitation when the actual system is complex and the mathematical model cannot capture all its dynamics. Model-free control addresses this limitation by using an ad-hoc simple model which is compensated by high-rate evaluation of dynamics in terms of their derivatives. However, application of the model-free control strategy to power electronics-based multi-time scale dynamical systems is challenging because of the derivative action needed to implement such control. Grid-connected power converters are examples of such systems, yet experimental validation has not been adequately addressed in the literature. This letter presents the validation of such control including the hardware implementation level. An intelligent proportional-integral (iPI) controller is synthesized and validated on a 16 kW experimental test bench. This proves the benefits of the approach in control of grid-connected power converters, among which their participation in the secondary voltage control.