#1 Grey-Box Experimental Identification of Reduced-Order Models for Grid-Forming Converters [PDF] [Copy] [Kimi] [REL]

Authors: Marcelo Cardenas, Stephan Kenzelmann, Matteo Saviozzi, Federico Silvestro, Fabrizio Sossan

This paper proposes a grey-box system identification for identifying and validating reduced-order models (ROMs) of grid-forming (GFM) converters. Three reduced-order modeling techniques are compared within a common identification procedure: singular perturbation with frequency cutoff and participation factors (SP-PF), singular perturbation with energy residuals (SP-Energy), and balanced truncation (BT). Testing is on experimental data with real-life components. Results show that BT achieves the highest time-domain fit, followed by SP-Energy and SP-PF; SP-Energy better preserves key properties of the identified full-order model; BT places the dominant mode closest to the stability boundary and exhibits the highest sensitivity to parameter variations; SP-Energy outperforms SP-PF in both fit quality and consistency of modal preservation. Findings suggest that the model with the best time-domain fit does not always provide the most reliable representation of the modal properties for small-signal stability, with SP-Energy offering the best compromise between accuracy, physical interpretability, and modal preservation for the considered case study.

Subject: Systems and Control

Publish: 2026-11-25 15:34:37 UTC