Temporary plastic film barriers are widely used to separate occupied rooms from exterior renovation zones, yet their effect on indoor particulate exposure is poorly quantified. We monitored PM2.5 in a Tampa, Florida, apartment for 48 days with a low-cost optical sensor (Temtop LKC-1000S+), spanning pre-barrier, barrier-on, and post-barrier periods. A quadratic baseline was fitted to "background" minutes devoid of identifiable indoor sources, allowing excess concentrations (ΔPM) to be partitioned into facade work, cooking, and passive accumulation without outdoor co-monitoring. The barrier prevented large construction spikes indoors but curtailed natural ventilation, doubling the mean baseline from 1.9 to 3.9 μg m−3. During this stage, passive build-up accounted for 45% of the daily excess dose, with facade work and cooking contributing 31% and 24%, respectively. Once the new window was installed and evening airing resumed, the baseline fell to 0.8 μg m−3, the lowest of the campaign. Our findings highlight the trade-off between dust shielding and background elevation and demonstrate that simple polynomial fitting bolsters low-cost IAQ diagnostics in mechanically unventilated dwellings. The framework is readily transferable to other retrofits; future studies should pair indoor sensing with outdoor references and multi-room deployments to refine infiltration estimates.